Package compact Substation are all factory assembled and tested. They are designed and manufactured in order to satisfy the customer’s specific requirements. The package substation is a combination of the Ring Main unit, Transformer and Low-Voltage panel.
| Description | Parameters |
|---|---|
| Rated Power | <2000 KVA |
| Rated voltage | 12 kV |
| Rated impulse withstand voltage | 75kVp |
| Rated Current of MV | 630 A |
| Maximum LV Current | 2000 A |
| RMU Rating | 12KV,630A,21KA(3 SEC) |
| Transformer Type | Oil or Dry Type |
| Transformer Rating | 1000 – 2000 KVA |
| Low voltage system Main incomer | up to 2000A |
| Short circuit Breaking capacity | 50Ka for 0.5 sec |
| Metering device | Digital AMR Type |
| Degree of Protection . | IP43 for (MV & LV), IP23 for Transformer and LVDB. Complete PSS for IP23D |
| Over all Dimensions | 3600 X 2600 X 2400 mm |
| Sheet metal material | Electro galvanized / Zinc Alu sheet |
| Powder color and category . | RAL 7032/7035 C3 or C5 for very high humid and corrosive environment |
| Ambient temperature (°C) | 50°C |
| Relative humidity | 100% |
| Ventilation Type | Natural |